36

Operation Theory

Waveform Generation Timing

Six counters interact with the waveform to generate different
DAWR timing, thus forming different waveforms. These are
described in Table 4-7.

NOTE

The maximum D/A update rate is 1 MHz. The minimum

UI_counter setting is 40.

Counter Name Width

Description

Note

UI_counter

24-bit

Update Interval, which
defines the update inter-
val between each data
output.

Update Interval =

UI_counter / Time-base*.

UC_counter

24-bit

Update Counts, which
defines the number of
data in a waveform.

When value in UC_counter

is smaller than the size of

waveform patterns, the

waveform is generated

piece-wisely.

IC_counter

16-bit

Iteration Counts, which
defines how many times
the waveform is gener-
ated.

DLY1_counter 16-bit

Define the delay time for
waveform generation
after the trigger signal.

Delay Time =

(DLY1_counter / Clock

Timebase)

DLY2_counter 16-bit

Define the delay time to
separate consecutive
waveform generation.
Effective only in Iterative
Waveform Generation
mode.

Delay Time =(DLY2_counter

/ Clock Timebase)

Trig_counter

16-bit

Define the acceptable
start trigger count when
re-trigger function is
enabled

Timebase*=40M for DAQ/

PXI-2500 Series

Table 4-7: Summary of Counters for Waveform Generation