PSSu E F 2DOR 8 (­T)(­R): Derating diagram for the permitted ambient temperature T de­
pendent on load current I

20

40

60

80

100

0

1

2

3

4

5

6

7

8

9

10

25

T [°C]

I [A]

45

4.1.2

Integrated protection mechanisms

When the PSSu E F PS1(­T) is used to supply the system, the module supply is buffered
for 20 ms if the supply voltage is interrupted.

The module has the following protection mechanisms:

}

1 monitored relay contact per output

}

Protective separation between both relay contacts (see Technical details)

}

Protective separation between both relay contacts and the periphery supply as well as
the module supply, in accordance with DIN VDE 0110 overvoltage category 2 in a pro­
tected industrial network

}

Temperature monitoring

The module provides the following diagnostic data:

}

Start­up error

}

Configuration error

}

FS communication error

}

Bus termination error

}

Temperature error: Too warm

}

Temperature error: Too hot

}

Relay control error

}

Relay error

4.1.3

Reaction times

Information on the reaction times of the outputs can be found in the PSSuniversal System
Description.