Pilz PSSu E F 2DOR 8 User Manual

Page 28

Advertising
background image

Technical details

Operating Manual PSSu E F 2DOR 8(­T)(­R)
21334­EN­07

28

Relay outputs

312225

314225

315225

Utilisation category

In accordance with the
standard

EN 60947­4­1

EN 60947­4­1

EN 60947­4­1

Safety contacts, AC1 at 250 V

250 V

250 V

Max. current

8,0 A

8,0 A

8,0 A

Min. current

10,00 mA

10,00 mA

10,00 mA

Max. power

2000 VA

2000 VA

2000 VA

Safety contacts, AC1
with condensation at

30 V

30 V

Min. current

10 mA

10 mA

Max. current

8 A

8 A

Max. power

240 VA

240 VA

Safety contacts, DC 1
at

24 V

24 V

24 V

Max. current

8,0 A

8,0 A

8,0 A

Min. current

10,00 mA

10,00 mA

10,00 mA

Max. power

192 W

192 W

192 W

Safety contacts, DC 1
at

60 V

Max. current

1,66 A

Min. current

10 mA

Max. power

100 W

Utilisation category

In accordance with the
standard

EN 60947­5­1

EN 60947­5­1

EN 60947­5­1

Safety contacts, AC15
at

230 V

230 V

230 V

Max. current

3,0 A

3,0 A

3,0 A

Safety contacts, AC15
with condensation at

30 V

30 V

Max. current

3 A

3 A

Safety contacts DC13
(6 cycles/min) at

24 V

24 V

24 V

Max. current

5,0 A

5,0 A

5,0 A

Safety contacts, DC1
at

60 V

Max. current

0,7 A

Utilisation category in ac­
cordance with UL

Voltage

250 V AC G.U. (same po­
larity)

250 V AC G.U. (same po­
larity)

With current

3,0 A

3,0 A

Voltage

24 V DC G. P.

24 V DC G. P.

With current

3,0 A

3,0 A

Pilot Duty

B300, R300

B300, R300

Advertising