Wiring

Operating Manual PSSu E F 2DOR 8(­T)(­R)
21334­EN­07

21

Functional earth: 2.5 mm

2

 (AWG12)

}

On base modules with screw terminals:

If you use a multi­strand cable to connect the I/Os, it is recommended that you use
ferrules conforming to Parts 1 and 2 of DIN 46228, 0.14 ... 1.5 mm

2

, Form A or C,

although this is not essential. To crimp the ferrules you can use crimp pliers (crimp
form A or C) conforming to EN 60947­1, such as the PZ 1.5 or PZ 6.5 from
Weidmüller, for example.

Maximum torque setting: 0.8 Nm

}

Use copper wiring.

6.2

Terminal configuration

Base module

Terminal configuration

With C­rail

11: Output O0
Relay contact 1

21: Not assigned

12­22: Output O0
Relay contact 2
(12­22 linked within the base
module)

13­23: C­rail supply 
(13­23­33­43 linked within
the base module)

14­24: Not assigned

31: Output O1
Relay contact 1

41: Not assigned

32­42: Output O1
Relay contact 2
(32­42 linked within the base
module)

34­44: Not assigned

21

11

22

12

23

13

24

14

41

31

42

32

43

33

44

34

Advertising