4 function test during commissioning, Function test during commissioning – Pilz PSSu E F 2DOR 8 User Manual
Page 23
Advertising
Wiring
Operating Manual PSSu E F 2DOR 8(T)(R)
21334EN07
23
Dualchannel actuator
Switches 230 VAC
21
11
22
12
23
13
24
14
O0
O0
n. c.
O1
n. c.
O1
C
41
31
42
32
43
33
44
34
L1
C
N
M
6.4
Function test during commissioning
An error must be simulated for each safetyrelated output during commissioning: The anti
cipated error reaction must occur when an output has a short circuit to a supply voltage.
INFORMATION
The short circuit test must be performed on the load and not on the output
terminal.