Wiring

Operating Manual PSSu E F 2DOR 8(­T)(­R)
21334­EN­07

23

Dual­channel actuator
Switches 230 VAC

21

11

22

12

23

13

24

14

O0

O0

n. c.

O1

n. c.

O1

C

41

31

42

32

43

33

44

34

L1

C

N

M

6.4

Function test during commissioning

An error must be simulated for each safety­related output during commissioning: The anti­
cipated error reaction must occur when an output has a short circuit to a supply voltage.

INFORMATION

The short circuit test must be performed on the load and not on the output
terminal.