Technical details

Operating Manual PSSu E F 2DOR 8(­T)(­R)
21334­EN­07

31

Environmental data

312225

314225

315225

Airgap creepage

In accordance with the
standard

EN 60664­1

EN 60664­1

EN 50124­1

Overvoltage category

III

III

OV2

Pollution degree

2

2

PD2

Protection type

In accordance with the
standard

EN 60529

EN 60529

EN 60529

Mounting area (e.g.
control cabinet)

IP54

IP54

IP51

Housing

IP20

IP20

IP20

Terminals

IP20

IP20

Mechanical data

312225

314225

315225

Mechanical life

10,000,000 cycles

10,000,000 cycles

10,000,000 cycles

Material

Bottom

PC

PC

PC

Front

PC

PC

PC

Coding

PA

PA

PA

Mounting type

plug­in

plug­in

plug­in

Dimensions

Height

76,0 mm

76,0 mm

76,0 mm

Width

25,2 mm

25,2 mm

25,2 mm

Depth

60,2 mm

60,2 mm

60,2 mm

Weight

99 g

99 g

99 g

Mechanical coding

Type

H

H

H

Colour

Yellow

Yellow

Yellow

The standards current on 2009­10 apply.

8.1

Safety characteristic data

Operating
mode

EN ISO
13849­1:
2008

PL

EN ISO
13849­1:
2008

Category

EN IEC
62061

SIL CL

EN IEC
62061

PFH

D

 [1/h]

IEC 61511

SIL

IEC 61511

PFD

EN ISO
13849­1:
2008

T

M

 [year]

1­channel

PL c

Cat. 1

­

7,60E­08

­

6,66E­03

20

2­channel

PL e

Cat. 4

SIL CL 3

7,78E­10

SIL 3

1,34E­06

20

If the module is operated at an ambient temperature above 60° C, the values stated in the
table for PFH

D

 and PFD will need to be doubled when a safety function is calculated.

All the units used within a safety function must be considered when calculating the safety
characteristic data.