Function description

Operating Manual PSSu E F 2DOR 8(­T)(­R)
21334­EN­07

14

4.2

Configuration

4.2.1

PSSu assignment in system environment A

Functions for the FS outputs of a PSSu are defined in the PSSuniversal Configurator on the
PSS WIN­PRO system software:

}

Read access through the standard bus system
(configured per module):
“R” configuration

}

Read/write access through the standard bus system 
(configured per FS output): 
"&" configuration (local enable principle)

}

Optimisation of ST process image by combining adjacent bits of the same type.
“*” configuration

INFORMATION

The PSSuniversal Configurator on the PSS WIN­PRO system software
must be used to define the I/O­Groups to which FS inputs and outputs be­
long (SafetyBUS p). The PSSu can be divided into sections A and B for this
purpose. All the FS outputs on a PSSu always belong to section A.

Section A and section B on a PSSu may belong to different I/O­Groups.

Further information on configuration is available in the PSSuniversal Configurator's online
help.

4.2.1.1

Addresses in the process image

The module occupies 4 consecutive bit addresses in the process image. The process im­
age in which the inputs are shown depends on the configuration.

Configuration

SafetyBUS p

Standard bus system

FS­PII

ST­PII

ST­PIO

None

4 Bit
(e. g.: 32.00 … 32.03)

­ ­ ­

­ ­ ­

Read ST (“R”)

4 Bit

­ ­ ­

4.2.2

PSSu assignment in system environment B

Data access is via pre­defined I/O data types:

I/O data name

I/O data type

I/O data element

Key

O0(11,21)

FS_O_DO

Data: SAFEBOOL

Output data O0

O1(31,32)

FS_O_DO

Data: SAFEBOOL

Output data O1

Advertising