4 register map – CIRCUTOR DHB Series User Manual

Page 30

Advertising
background image

30

6.4 Register Map

The register map of the DHB-224 meter is presented below.

Notice:
All given addresses are physical addresses. In some computer pro-
grams logical addressing is applied, then addresses must be increa-
sed of 1.

Table 8

Range of addreses

Value type

Description

4000-4049

integer (16 bits)

Value placed in a 16-bit register.

7000-7025

float (32 bits)

Value placed in two successive 16-
bit registers. Registers include the
same data as 32-bit register from
the area 7500. Registers are only for
readout.

7200-7363

float (32 bits)

Value placed in two successive 16-
bit registers. Registers include the
same data as 32-bit register from
the area 7600. Registers can be
read out and written.

7500-7512

float (32 bits)

Value placed in a 32-bit register.
Registers are only for readout.

7600-7663

float (32 bits)

Value placed in a 32-bit register.
Registers can be read out and
written.

Advertising