CIRCUTOR DHB Series User Manual

Page 35

Advertising
background image

35

Bit 15

Break of the supply

Bit 14

Re-set of the RTC clock.

3

38400 bit/s

4

57600 bit/s

5

115200 bit/s

Meter address. The write of the value 0 causes the

inerface switching off.

4033

Addr

z/o

0...247

Transmission mode

4032

prot

z/o

0...3

Update transmission parameters. Causes the appli-

cation of introduced RS-485 interface settings.

4034

sAvE

z/o

0...1

Value

0

RTU 8N2

1

RTU 8E1

2

RTU 8O1

3

RTU 8N1

Description

Write of standard parameters

4035

SEt

z/o

0...1

Value

0

without changes

1

set standard parameters

Description

Password for parameters

4036

SEc

z/o

0...6000

Value

0 without password

...

Entry in parameters preceded by a

request about the password

Description

Current time

4037

hour

z/o

0...2359

This parameter occurs in the ggmm format,where:

gg - means hours,

mm – means minutes.

The introduction of a wrong hour will cause the set-

ting 23, however the introduction of wrong minutes

will generate the setting of the value 59.

Switch on/off the unit backlight

4038

unit

z/o

0, 1

Value

0

Highlighting switched off

1

Highlighting switched on

Description

Reserved

...

...

...

...

Meter status. Describes the current state of the
meter. Successive bits present data of the event.
The bit set on 1 means, that the event took place.
Events can be only erased..

4048

Status1

z/o

0...65535

4039

z/o

0, 1

Extreme values’ deletion. Writing in “1” to the

register will cause the deletion of the minimum and

maximum values