Installation – Avalon Firestyles DVL Fireplace EF-2003 to 2007 User Manual

Page 19

Advertising
background image

Installation

(for qualified installers only)

1 9

Travis Industries

4041206

1 0 0 - 0 1 1 4 7

Vent Installation

In addition to the requirements below, follow the requirements provided with the vent.

Vertical Termination
(part # 1291)

Use a roof flashing and storm collar
whenever passing through the roof

Vertical Vent

Requirements

Horizontal Vent

Requirements

Min. 1" Clearance on
Vertical Sections to
combustible surfaces.

Use a firestop whenever passing through a
ceiling (or enclosure and at every floor
penetration.

Combustible
Framing

Use the Travis Firestop (part # 93006094) when passing through a
wall. NOTE: make sure the firestop is postitioned correctly so the 3"
clearance is allowed above the vent.

3" Min.

1" Min.

1" Min.

Combustible
Surfaces

Slide the vent sections together and turn 1/4 turn until the sections lock in
place.

Screws are not required to secure the vent. However, three screws may be
used to secure vent sections together if desired.

High temperature sealant is recommended at the appliance starter section
connection (use high-temperature silicone or Mill-Pac®).

If disassembly is required, at time of re-assembly check to see if the vent
creates a tight fit. If it does not, apply high temperature sealant to the joints of
the affected sections.

Horizontal sections require a 1/4" rise every 12" of travel

Horizontal sections require non-combustible support every three feet (e.g.: plumbing tape)