Installation

(for qualified installers only)

Travis Industries

4041206

1 0 0 - 0 1 1 4 7

Fireplace Placement Requirements

Minimum Framing Dimensions

A 1" clearance is required along the sides and back of the fireplace. The 1" stand-offs on the sides
and 6-3/8" stand-offs on the top of the fireplace are designed to separate the fireplace from the
framing members. These stand-offs may contact the framing members but no material may be placed
between the stand-offs.

54-3/4" Min.

44-1/4"

20-1/2"

46-3/4"

3" Clearance Min. Above Vent

The center of the vent is a
minimum 47-3/4" above the
base of the fireplace.

1" Clearance Min. to
the Sides of Vent

The fireplace enclosure
must not be less than
54-3/4" above the base
of the fireplace.

1" Clearance Min.
Below Vent

Fireplace must be installed on a level surface capable of supporting the fireplace and vent

Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet)

This heater may be placed in a bedroom. Please be aware of the large amount of heat this appliance
produces when determining a location.

Clearances

When installed, walls in front of the fireplace must be a minimum 6" to the side of the faceplate.

Due to the high temperature of the fireplace, it should be located out of traffic and away from furniture
and draperies.

Fireplace must be placed so the vents below and above the glass do not become blocked