Problem 2: Measured Current Magnitude Mismatch
General

The currents measured by each set of current inputs can be transformed from their primary values by

different CT ratios. This is illustrated in Figure 1-2. When the zone of protection includes a transformer,

there is another source of magnitude mismatch that must be accounted for. The primary currents that the

differential relay must monitor will be on different voltage bases in most cases. This is due to the

transformer action; the current on each side of the transformer is transformed by the inverse of the

voltage transformation ratio. This is illustrated in Figure 1-3.

BE1-CDS240 Solution

The BE1-CDS240 relay applies a tap adjustment factor to the measured currents to cancel the effect of

dissimilar CT ratio and voltage bases by converting the currents to per unit quantities on a common base.

The tap-adjusted currents are used by the percentage restrained differential protection functions to

determine the restraint and differential currents. Thus, the mismatch in magnitudes under normal

balanced conditions is eliminated. The tap adjustment factor can be manually entered or automatically

calculated by the relay using parameters entered for each CT input circuit and for the differential tap

settings.
The setup parameters for each of the current input circuits are described in Section 3, Input and Output

Functions, Power System Inputs. The CT ratio is included to allow the currents to be metered, displayed,

and reported in primary values. The CT ratio is also used as a parameter for the automatic tap calculation

feature.

Figure 1-2. Tap Adjust for Mismatch

Figure 1-3. Currents on Different

Voltage Bases


The setup parameters for the tap adjustment factor are described in Section 4, Protection and Control,

Differential Protection. The user can enter the megavolt ampere (MVA) base for the application and the

kilovolt (kV) base for each current input and the relay will automatically calculate the taps using these

settings and the settings for each current input circuit. Alternatively, the user can enter the taps directly for

each CT input.

Problem 3: Mismatch Caused by Load Tap Changers
General

The voltage transformation ratio (and thus the current transformation ratio) of a transformer within the

zone of the differential can be adjusted in service by typically ±10% with the use of load tap changers.

D2837-18

12-14-98

600:5

400A

600:5

400A

600:5

400A

CDS

1200:5

1200A

5.0 A

Secondary

10.0 A

Secondary

Input 1 Tap = 5

Input 2 Tap = 10

So 5A = 1 x Tap

10A = 1 x Tap

Current-out balances current-in (in multiples of tap).

40A

D2837-17.vsd

12-14-98

2400/240 Volts

H

1

H

0

400A

X

1

X

0

9365200990 Rev M