87nd neutral differential protection, Restrained differential (87ndpu, 87ndt), Pickup accuracy – Basler Electric BE1-CDS240 General Information User Manual

Page 24: Tap setting range, Restraint slope, Automatic setting group characteristics, Switch level, Switch timer, Bestlogic, General specifications

Advertising
background image

Figure 1-9. Typical 87 Response Characteristic Curves

87ND Neutral Differential Protection
Restrained Differential (87NDPU, 87NDT)

Pickup Accuracy

5 Ampere CT ............................................................ ±4% or ±75 mA, whichever is greater

1 Ampere CT ............................................................ ±4% or ±25 mA, whichever is greater

TAP Setting Range

5 Ampere CT ............................................................ 2 to 20 A

1 Ampere CT ............................................................ 0.4 to 4 A

Minimum Pickup (1 or 5 Ampere CT)

Setting Range .......................................................... 0.10 to 1.00 per unit

Restraint Slope

Setting Range (1 or 5 Ampere CT) .......................... 15 to 60%

Automatic Setting Group Characteristics

Number of Setting Groups:

4

Switch Level

Range ............................................................................. 0-150% of the setting group 0 #51 Phase, Neutral,

or Negative-Sequence pickup setting

Accuracy ......................................................................... ±2% or ±50 mA (5 A), ±2% or ±10 mA (1 A)

Switch Timer

Range ............................................................................. 0-150% of the setting group 0 #51 Phase, Neutral,

or Negative-Sequence pickup setting

Accuracy ......................................................................... ±0.5% or ±2 s, whichever is greater

BESTlogic

Update Rate .................................................................... ¼ cycle

General Specifications

AC Current Inputs
5 Ampere CT

Continuous rating ............................................................ 20 A

One second rating .......................................................... 400 A
For other current levels, use the formula I = (K/t)

½

where t = time in seconds and K = 160,000.

Begins to Clip (saturate) ................................................. 150 A

Burden ............................................................................ <10 mΩ at 5 Aac

0.00

0.50

1.00

1.50

2.00

2.50

3.00

3.50

0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0

R

esp

on

se

Ti

me (

cycl

es)

Multiple of Pickup

Unrestrained
Restrained

1-22

BE1-CDS240 General Information

9365200990 Rev M