Input burden, Recognition time, Irig – Basler Electric BE1-CDS240 General Information User Manual

Page 26: Real-time clock, Communication ports, Interface, Irig -24, Real-time clock -24, Communication ports -24, Table 1-2. contact-sensing input burden -24

Advertising
background image

Input Burden

Burden values shown in Table 1-2 assume nominal value of input voltage applied.

Table 1-2. Contact-Sensing Input Burden

Style Option Nominal Input Voltage

Burden

Jumper (L)

(Low Position)

Jumper (H)

(High Position) Jumper Not Installed

xxxx1xxxxxx

48 Vdc or 125 Vac/dc

22 kΩ

53 kΩ

n/a

xxxx2xxxxxx

125/250 Vac/dc

66 kΩ

123 kΩ

n/a

xxxx3xxxxxx

24Vdc

n/a

n/a

6 kΩ

Recognition Time

Programmable, 4 to 255 ms

NOTE

All timing specifications are for the worst-case response. This includes output

contact operate times and standard BESTlogic operation timing but excludes

input debounce timing and non-standard logic configurations. If a non-standard

logic scheme involves feedback, then one or more BESTlogic update rate

delays must be included to calculate the worst-case delay. An example of

feedback is virtual outputs driving function block inputs. For more information,

see Section 7, BESTlogic Programmable Logic.

IRIG

Standard ......................................................................... 200-98, Format B002

Input Signal ..................................................................... Demodulated (dc level-shifted digital signal)

Logic-High Voltage ......................................................... 3.5 Vdc, minimum

Logic-Low Voltage .......................................................... 0.5 Vdc, maximum

Input Voltage Range ....................................................... +10 to −10 Vdc

Resistance ...................................................................... Nonlinear, approximately 4 kΩ at 3.5 Vdc,

approximately 3 kΩ at 20 Vdc

Real-Time Clock

Accuracy ......................................................................... 1 second per day at 25°C (free running) or ±2

milliseconds (with IRIG synchronization)

Resolution ....................................................................... 1 millisecond

Date and Time Setting Provisions .................................. Front panel, communications port, and IRIG. Leap

year correction provided.

Clock Power Supply Holdup Capacitor ........................... 8 to 24 hours, depending on conditions

Clock Power Supply Holdup Battery ............................... Greater than 5 years

Backup Battery (Optional) .............................................. Lithium battery 3.6 Vdc, 0.95 AH,

Basler Electric p/n: 9318700012 or

Applied Power p/n: BM551902

Communication Ports
Interface

Front RS-232 .................................................................. 300 to 19,200 baud, 8N1, full duplex

Rear RS-232 ................................................................... 300 to 19,200 baud, 8N1, full duplex

Rear RS-485 ................................................................... 300 to 19,200 baud, 8N1, half duplex