Section 1 • general information, Introduction, Features – Basler Electric BE1-CDS240 General Information User Manual

Page 3: Section 1 • general information -1, Introduction -1, Features -1

Advertising
background image

SECTION 1 • GENERAL INFORMATION

Introduction

The BE1-CDS240 Current Differential System is an economical, microprocessor based, multifunction

system that provides a four input, three-phase percentage differential with harmonic restraint protection.

Also included is three-phase with voltage control, ground, and negative-sequence overcurrent protection,

voltage and frequency protection, breaker failure for up to four breakers, breaker monitoring for four

breakers, transformer monitoring, and metering functions, all in an integrated system with several

communications options. The BE1-CDS240 Current Differential System is intended for use in any low

impedance current differential protection application including transformer, generator, motor, and bus

protection. Four setting groups are provided for adaptive relaying with automatic selection logic for cold

load pickup and/or dynamic setting group changes.
The BE1-CDS240 can be ordered with 12 programmable contact sensing inputs, 10 programmable

outputs, and one alarm output or eight programmable contact-sensing inputs, 14 programmable outputs

and one alarm output. Outputs can be assigned various functions by logical programming to perform

protection, control, or indicate operations. For example, protection functions can cause a protective trip

operation. Control functions can cause a manual trip, manual close, or automatic reclose operation.

Indicators could be relay alarm, setting group one enable, setting group two enable and others.
Protection scheme designers may select from an embedded pre-programmed logic scheme or from a

number of logic library schemes found in BESTCOMS™ to perform the most common protection and

control requirements or create a custom scheme using BESTlogic.
The BE1-CDS240 is available in a fully draw-out MX case with configurations for horizontal 19" rack

mounting, horizontal panel mounting and vertical panel mounting. BE1-CDS240 features include:

Up to four restraint inputs (four three-phase current circuits) and two virtual current circuits

that can be used with any combination of two current inputs

Independent ground input

Three voltage inputs (Va, Vb, Vc, to Vn)

Three-phase percentage differential protection with harmonic restraint

Three-phase voltage, frequency and overcurrent protection

Four setting groups

One embedded preprogrammed logic scheme

Fourteen or 10 programmable outputs

Eight or 12 contact sensing inputs

Breaker failure protection for four breakers

Front panel HMI (human-machine interface)

Communications ports: one front RS-232, one rear RS-232, one rear RS-485 and one rear

IRIG port

Communications protocols available: DNP3, Modbus™ RTU, and ASCII

Sequence of events recording

Fault recording

Oscillography

Demand reporting

Differential current monitoring

Optional load profile reporting

Section 2, Quick Start, provides BE1-CDS240 Current Differential System users with a simplified, "How

To Get Started" procedure.

Features

The BE1-CDS240 includes many features for the protection, monitoring, and control of power system

equipment such as transformers, breakers, buses, generators, and motors. These features include
9365200990 Rev M

BE1-CDS240 General Information

1-1

Advertising