Basler Electric BE1-CDS240 General Information User Manual

Page 14

Advertising
background image

Figure 1-5. Three-Phase Connections, Delta-Wye Configuration, CT Compensation


There are several drawbacks to the traditional solution:

The delta connection requires a dedicated set of CTs that generally cannot be used for other

purposes.

The delta connection is more difficult to test.

The delta-connected CTs experience greater burden than wye-connected CTs because the lead

burden must be multiplied by a factor of three in the CT performance calculation.

The BE1-CDS240 relays support the traditional solution so that they may be used in retrofit/modernization

projects. However, in a numerical relay, it is possible to connect all of the CTs in wye as shown in Figure

1-6 so that the drawbacks mentioned above are not a consideration. The BE1-CDS240 relay can

numerically combine currents internally to accomplish a numerical delta if required for phase angle

compensation.
The setup parameters for each of the current input circuits are described in Section 3, Input and Output

Functions, Power System Inputs. The CT connection and the transformer connection are included to

allow the BE1-CDS240 relay to automatically determine the appropriate combination of currents to

present to the differential protection function.

NOTE

The BE1-CDS240 relay uses transformer internal connection information to

determine the correct phase compensation to use. It is not possible to reliably

determine the phase compensation settings based simply upon phase angle

shift information because the phase shift from high to low side is dependent

upon the phase-sequence of the power system phasors. That is, a power

system with ABC phase-sequence will produce a different phase shift from

high to low than a power system with ACB phase-sequence in the same

transformer connection. By specifying the transformer connections from the

three-line diagram, the correct phase compensation can be determined in all

cases.

H

2

H

1

H

3

C

B

A

X

2

X

1

X

0

X

3

C

B

A

A13

A14

A9

A11

A7

A8

A5

A6

*

BE1-CDS240

*An alternative to grounding one corner of the delta connected CTs is

to connect the ground to a lead connected to terminal A10, 12, or 14.

P0017-03