Seventy (70) alarm conditions are available to be monitored including user definable logic

conditions using BESTlogic.

Version Report

The version of the embedded software (firmware) is available from the front panel interface HMI

or the communications ports.

The unit serial number and style number is also available from the communications ports.

BESTlogic Programmable Logic

Each of the protection and control functions in the BE1-CDS240 is implemented in an

independent function that is equivalent to its single function, discrete device counterpart so that it

is immediately familiar to the protection engineer. Each independent function block has all of the

inputs and outputs that the discrete component counterpart might have.

Programming BESTlogic is equivalent to choosing the devices required by your protection and

control scheme and drawing schematic diagrams to connect the inputs and outputs to obtain the

desired operational logic.

One preprogrammed embedded logic scheme (in the relay firmware) and a library of

preprogrammed logic schemes in BESTCOMS are provided and thoroughly documented in

Section 8, Applications. To set the relay to one of the BESTCOMS library applications, simply

select the logic scheme and upload it to the relay.

A set of custom logic settings is also available for you to optimize the functionality to the specific

needs of your operation's practices and power system requirements.

Security

Security can be defined for three distinct functional access areas: Settings, Reports, and Control.

Each functional access area can be assigned a password. A global password provides access to

all three functional areas. Each of these four passwords can be unique or multiple functional

access areas can have the same password.

Allowing the user to restrict access to any of the three functional access areas from only specific

communication ports provides a second dimension of security. For example, you could set

security to deny access to control commands from the rear RS-232 port that is connected through

a modem to a telephone line.

Security settings only affect write access. You have read access from any port to any area.

Human-Machine Interface

Each BE1-CDS240 comes with a front panel display with LED (light emitting diode) indicators for

power, relay trouble alarm, minor alarm, major alarm, and trip. Each BE1-CDS240 also comes

with the software application program BESTCOMS for the CDS240. This program is a user

friendly, Windows based program that makes relay setup and support very easy.

The programmable graphical LCD (liquid crystal display) allows the relay to replace local

indication and control functions such as panel metering, alarm annunciation, and control

switches.

The human-machine interface (HMI) is set up in a menu tree with four scrolling buttons for

navigation. Edit and Reset pushbuttons provide access to change parameters and reset targets,

alarms and other registers. Scrolling buttons are used for data entry when in edit mode. Edit

mode is indicated by an LED on the Edit button.

The LCD has automatic priority logic to govern what is being displayed on the screen so that

when an operator approaches, the information of most interest is automatically displayed without

having to navigate the menu structure. The priorities are targets, then alarms and then the

programmable automatic scrolling list.

Up to 16 screens can be defined in the programmable, automatic scroll list.

ASCII Command Interface

Three (3) independent, isolated communications ports provide access to all functions in the relay.

Com 0 is a 9-pin RS-232 port located on the front of the case. Com 1 is a 9-pin RS-232 port

located on the back of the case. Com 2 is a three-terminal, RS-485 port located on the back of

the case.