Energy data reporting, Range, 24 overexcitation protection – Basler Electric BE1-CDS240 General Information User Manual

Page 20: Pickup, Integrating time delay, Definite time delay, 27p phase undervoltage protection, Time delay, 47 negative-sequence voltage protection, Energy data reporting -18

Advertising
background image

Energy Data Reporting

Range

1 or 5 Ampere CT ..................................................... 100 MWh

Units of Measure ............................................................. kilo, mega, giga

Rollover Value of Registers ............................................ 100,000

Accuracy ......................................................................... ±1% at unity power factor

24 Overexcitation Protection
Pickup

Setting Range ................................................................. 0.5 to 6 V/Hz

Accuracy ......................................................................... ±2%

Integrating Time Delay

Time Dial ......................................................................... 0.0 to 9.9

Reset Dial ....................................................................... 0.0 to 9.9

Accuracy ......................................................................... 5% or 4 cycles, whichever is greater

n

NOMINAL

MEASURED

T

1

HZ

V

HZ

V

DT

T

=

Time to Trip


100

*

FST

E

*

D

T

T

R

R

=


Time to Reset

where:

T

T

= Time to trip

T

R

= Time to reset

D

T

= Time dial trip

D

R

= Time dial, reset

E

T

= Elapsed time

n = Curve exponent (0.5, 1, 2)

FST = Full scale trip time (TT)

ET/FST = Fraction of total travel toward trip that integration had progressed to. (After a trip,

this value will be equal to one.)

Definite Time Delay

Time Delay ...................................................................... 0.050 to 600 s

Accuracy ......................................................................... 5% or 4 cycles, whichever is greater

27P Phase Undervoltage Protection
Pickup

Setting Range ................................................................. 10 to 300 V

Accuracy ......................................................................... ±2% or ±1 V, whichever is greater

Dropout/Pickup Ratio ...................................................... 102%

Time Delay

Setting Range ................................................................. 0.050 to 600 s

Accuracy ......................................................................... ±0.5% or ±1 cycle, whichever is greater

47 Negative-Sequence Voltage Protection
Pickup

Setting Range ................................................................ 1.0 to 300 V

L-N

Accuracy ......................................................................... ±2% or ±1 V, whichever is greater

Dropout/Pickup Ratio ...................................................... 98%

1-18

BE1-CDS240 General Information

9365200990 Rev M