2.12 Wiring Alarm and External Lockout

(optional)

External alarm

To connect an external alarm to your system,
put a wire on each side of the closing contacts
marked EXT ALARM.

Note: The external alarm needs to have an
independent power source.

External lockout

To enable the external lockout function on your
Dosetronic, a switch needs to be connected to
the external lockout wiring terminal on the alarm
circuit board (see diagram on page 14). There
are two types of switches that can be wired in:
those that are normally open and those that are
normally closed.

For example: If you connect a flow switch (that
opens when water stops flowing) to the normally
closed port, the external lockout function will
sense that the water has stopped and stop your
system from dosing.

Note: If you are not using any NC switches in
your system, ensure factory link is installed.

Common

Normally Closed

Normally Open

Connect multiple normally

closed switches in series

Connect multiple normally

open switches in parallel

2

- +

EXT ALARM

Refer to specifications for

maximum power rating

Parallel

Series

COM
NC
NO

COM
NC
NO