10

C– S C+

For data for air and electrical
connections, see section
Technical Data on page 48.

Connections

Air:

Port S

Supply air, 2-7 bar

Port C+

Connection to actuator

Port C-

Connection to actuator
(only for double action)

Electrical connection

See page 12, 13.

Dimensions

Air connections:
1/4" NPT alt. G 1/4"
Electrical connection:
M20 x 1.5 alt. NPT 1/2"

Loctite 577 or equivalent is recommended
as a sealant.

Must be plugged when converting to
single action function.

The D3 Ex positioner has an ISO F05

footprint, A. The holes are used to attach it
to the mounting bracket B, which is suitable
for most types of linear actuators.

The spindle adapter C can be changed to

suit the actuator in question, see previous
page.