Flowserve PMV D3 Digital Positioner User Manual

Page 12

Advertising
background image

12

Option

HART-
connection

1

4-20 mA + input signal

2

4-20 mA – input signal

3

Switch 1 NO

4

Switch 1 NC

5

Switch 1 COM

6

Switch 2 NO

7

Switch 2 NC

8

Switch 2 COM

9

AUX input 4-20 mA +

10 AUX input 4-20 mA –
11 4-20 mA + Feedback, 10-28 V DC
12 4-20 mA – Feedback, 10-28 V DC
13 Alarm output +
14 Alarm output –

+ –

+ – + – + –

1

2

3

4

5

6

7

8

9

10

11

12 13

14

Remote-
unit

+ –

1

2

3

4

5

6

3

4

5

Shielded cables,
grounded on the D3

Connecting a
remote unit

D3

The terminal block (below) for the posi-

tioner is accessible when the aluminium cover
and inner cover is removed, see Section 8.

Warning! In a hazardous
environment where there is a
risk of explosion, electrical
connections must comply with
the relevant regulations.

Electrical connections

The diagrams show the terminal blocks

in D3 and D3 Ex.

Remote unit

The remote unit shall be connected

between terminals3, 4 and 5 in the D3 and 3,
4 and 5 in the remote unit. Use a shielded
cable and ground it in the D3 only. Max
recommended distance between D3 and
remote unit: 5 m.

Note! When converting D3/D3 Ex for use

with remote unit, some changes have to be
done inside the positioner, see Section 8.

When installing D3 Intrinsically safe unit, always consider cdwg D3-70.