Flowserve PMV D3 Digital Positioner User Manual

Page 26

Advertising
background image

26

TRVL range

Setting end positions

0%=0.0%

Select Out of Service.
Set percentage value
for desired end posi-
tion (e.g. 3%).

Set 0%

Select In Service.
Connect calibrator.
Move forward to desired
end position (0%) and
press OK.

100%=100.0%

Select Out of Service.
Set percentage value for
desired end position (e.g.
97%).

Set 100%

Select In Service.
Connect calibrator. Move
forward to desired end
position (100%) and
press OK.

Trvl ctrl

Behaviour at set end
position

Set low

Choose between Free (go
to mechanical stop),
Limit (stop at set end
position), and Cut off (go
directly to mechanical
stop at set end position).

Set high

Similar to Set low.

Values

Select position for Cut off
and Limit at the
respective end positions.

Passcodes

Setting passcodes for
various functions

Full menu

Passcode for access to
full menu.

Write prot

Passcode for removing
write protect.

Expert

Passcode for access to
Expert menu (TUNING).

Fact set

Passcode to return to
default values applicable
when positioner was
delivered.

Numbers between 0000 and 9999 can be used as
passcodes. 0 = no passcode required.

Appearance

On display

Language

Select menu language.

Units

Select units.

Def. Display

Select value(s) to be
displayed during service.
The display reverts to
this value 10 minutes
after any change is made.

Start menu

Start in Basic menu or
Full menu.

Contrast

Adjust display contrast.

Orient

Orientation of text on
display.

Par mode

Display of control para
meters such as P, I, D or
K, Ti, Td.

Devicedata
HW rew
SW rew

General parameters.

Capability
HART

Menu with HART para-
meters. Only amendable
with HART communi-
cator. It is possible to read
from display.

Profibus
Status

Indicates present status

Device ID

Serial number

Address

1-126

Tag

Allotted ID

Descriptor

ID description

Date

N/A

Failsafe

Value = preset pos
Time = Set time +10sec=
time before movement
Valve act = failsafe
(preset pos) or lastvalue
(present pos)
Alarm out= On/Off