6. Installation

Tubing

Use tubes with an inner diameter of mi-

nimum 6 mm (1/4”).

Air supply requirements

Max. air supply pressure, see the section

Technical Data, Section 10.

The air supply must be free from

moisture, water, oil, and particles.

The air must come from a refrigeration

dried supply or be treated in such a way that
its dew point is at least 10

°C (18°F) below

the lowest expected ambient temperature.

To ensure a stable and problem-free air

supply, we recommend the installation of a
filter/pressure regulator <40

µ as close to the

positioner as possible.

Before the air supply is connected to the

positioner, we recommend the hose is opened
freely for 2 to 3 minutes to allow any con-
tamination to be blown out. Direct the air jet
into a large paper bag to trap any water, oil,
or other foreign materials. If this indicates
that the air system is contaminated, it should
be properly cleaned.

WARNING! Do not direct the
open air jet towards people or
objects because it may cause
personal injury or damage.

Poor air supplies are the main source

of problems in pneumatic systems.