The contents of the menu are shown on the next page. The various menu
texts are described below.

Auto-Cal

Auto-tuning and calibration of end positions

Start tune

Starts the tuning. Questions/commands are displayed during
calibration. Select the type of movement, function, etc. with

and confirm with OK as shown in the chart on the next

page.

Lose prev value? OK?

A warning that the value set previously will be lost (not during
the first auto-tuning).

Actuator? rotating

Select for rotating actuator.

Actuator? linear

Select for linear actuator.

Actuator single act

Select for single act.

Actuator double act

Select for double act.

Direction? direct

Select for direct function.

Direction? reverse

Select for reverse function.

In service? Press OK

Calibration finished. Press OK to start positioner functioning.
(If ESC is pressed, the positioner assumes the ”Out of service”
position but the calibration is retained).

TravelCal

Calibration of end positions

Start cal

Start end position calibration.

Lose prev value? OK?

A warning that the previously set value will be lost.
Confirm with OK.
The calibration sequence starts.

In service? Press OK

Calibration finished. Press OK to start positioner functioning.
(If ESC is pressed, the positioner assumes the ”Out of service”
position but the calibration is retained).

Perform

Setting gain

Normal

100% gain

Perform 50%, 25%,
12%, L, M, S

Possibility to select a lower gain in steps.

L, M, S

Preset values for L, M, S actuators

Factory set

Resets all set values and enters Factory Mode. Should only
be used by authorized staff.

Note. Original P. I. D. will always be shown in display