Stroke Characterization

In addition to three pre-defined and embedded characterization curves, the Logix 3400IQ digital positioner
has a 21-point custom stroke characterization feature. This allows the user to define a unique set of
operating parameters customizable to his process conditions.


Table 2: Transducer Block Characterization Parameters

Parameter

Description

Value — Meaning

Comments

MODE_BLK

The operating

mode of the

transducer block

Permitted Modes:

Auto - Auto

(target

mode)

OOS - Out of

Service

The transducer

block must

be

out-of-service

before the

user

can edit or

change

characterization.

1 Quick Opening

Curve*

Loads

factory

defined QO

curve as custom

curve.

2 Equal Percent Curve

Loads factory defined equal
percent curve as custom
curve.

3 Actuator Type

4 Positioner Model

5 ActuatorStyle

6 Custom Characterization
Active

Activates custom curve. If
Off, response is Linear.

7 Fail Position

CONTROL_FLAGS Byte values

which select

positioner

operation

features

8 Air Action

CURVEX

Numeric X value

array for

custom

point.

(1x21 array

points)

X-axis value for custom

stroke characterization

point.

Range

-10 to 110

Pair each

X-value with

corresponding

Y-value to

define the

desired point.

Values must be

in

ascending

(or equal)

order.

CURVEY

Numeric Y value array for
custom point. (1x21 array
points)

Y-axis value for custom
stroke characterization point.
Range -10 to 110

* Must not be selected if a custom curve is to be created or edited.