Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07

RAMP_RATE

*

Desired rate (% per

Minute)

for ramp

%/Min. Minimum value is
1.0

Typically this is set to
100. Very

long times

could result in
completely

filling the

10K RAM buffer.

Can

only be set when

STEP_RAMP in
SIG_FLAGS has

been

selected.

SAMPLE_TIME

Data acquisition time

between samples

Seconds. Range 0.1 to
2.55.

Set to a valid value

before

running signature.

Typically

0.1

Determines the
number of data

points

stored in the
signature.

STEP_TIME*

Delay time after step

Seconds. Range 0-650.0
Typically

set to 0.1

Allows settling time to
capture

valve

response to the step.
Can

only be set when

STEP_RAMP in

SIG_FLAGS is not
selected.

SIG_INDEX

Pointer used for data

transfer

Write the desired packet

value.

Writing a value
between 1 and

the

max number shown in

SIG_COUNTER
moves that

packet of

data into the
SIG_DATA

array for

retrieval.

SIG_COUNTER

Indicates number of

data

points collected

Increments by 1 as each
data

packet is collected

Order of data is:

Command (%)

Position (%)

Port 2 pressure

SIG_DATA

Array for the storage

and

transfer of signature

data

Port 1 pressure

STROKE_TSTPSI

Supply pressure in

PSI for

stroke test

150 psi max.

STROKE_OPENTIM

Stroking time during

opening

Seconds

Determined during the
last stroke

calibration

where the Step Time

Test option was ran

STROKE_CLOSEDTIM Stroking time during

closing

Seconds

Determined during the
last stroke

calibration

where the Step Time

Test option was ran

* Special Note: Because of the internal Database size limit of 10K within the Fieldbus device, the values for

RAMP_RATE or STEP_TIME may be recalculated to the most reasonable value to allow using the database.
The

new value will appear in the parameter after the desired one is written. This is done to prevent accidental

overflow

of the database.