Initiating a valve signature – Flowserve 3400IQ User Manual

Page 28

Advertising
background image

Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07

Initiating a Valve Signature


A feature of the Logix 3400IQ digital positioner is the ability to capture and store a valve diagnostic signature
in the positioner’s volatile RAM. A signature is the collected data response of the valve to a pre-defined set
of operating conditions. This stored data can later be uploaded to the host system for analysis of potential
problems. By comparing a baseline signature (when the valve is new) to subsequent signatures at later
times, a rate of change can be tracked which can help predict possible faults in the valve before they
happen. This is called ‘predictive maintenance’.

NOTE: The purpose of the positioner is to act as the data acquisition device for the signature. Analysis of
the data is not done on the device, but in the supervisory system.

System Preparation

WARNING: By definition, the collection of the signature requires the unmanaged operation of the

positioner. Therefore, the process must be in a safe operating mode where unexpected movement of the
valve will not cause a hazardous condition.

Before a valve signature can be run, the Transducer block must out of service.


Table 3: Transducer Block Signature Parameters

Parameter

Description

Value-Meaning

Comments

MODE_BLK

The operatingmode of

the

transducer block

Permitted Modes:

Auto - Auto (target mode)

OOS - Out of Service

The transducer block
must be in

the OOS

mode to perform a
signature

0 - VALVE INIT Initializes

valve for signature
capture.

Read-only

1 - STEP_RAMP Selects
which type of signature is
desired. Select for ramp
signature.

2 - SIG_COMPLETE
Status byte set when the
signature has been
completed, Read-only

4 - PRESS_MEAS
Selects if actuator
pressure readings are
desired as part of the
signature. Select for
readings

SIG_FLAGS

Byte values which

select

which signature

options are

used

5 - BEGIN_SIG Set to
initiate the signature
routine.

Select the desired
signature

options and

then make sure the

signature parameters
are set to

the desired

operation before

beginning the
signature.

SIG_START

Beginning position

point (%)

for signature

-10% to 110%

position range

Set higher than the stop
position

for a valve

closing signature.

SIG_STOP

Ending position point

(%) for

signature

-10% to 110% position
range

Set lower than the
starting position

for a

closing signature

28