Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07

Pressure Calibration: To perform a pressure calibration, complete the following steps:

Set the Transducer block to OOS.

Check the periodic update box under the Custom tab, in the Transducer Block window.

Ensure the positioner is an advance model (see parameter CONTROL_FLAGS).

Ensure air supply.

Set PRESS_CAL to air supply pressure value.

Set PRESS_UNITS to the proper pressure units

Select Perform Pressure Calibration option under the CALIBRATE parameter in the NI Configurator.

Click the Write button.


The valve should now go closed, then open. CALIBRATE will return to normal operation at the completion of
the calibration process.



























21