Logix 3400IQ Digital Positioner FCD LGENIM3403-00 – 11/07

A

B

C

D

E

F

G

H

A. Transducer Block

B. Logix 3400IQ Digital Positioner

C. Function Blocks

D. Function Block Tag Name

E. Function Block Type

F. Main Configurator Window

G. Status Window

H. Help Window


Figure 4: NI Configuration Set-up Window

Connect the Logix 3400IQ digital positioner to the fieldbus. One of the LEDs on the Logix 3400IQ digital
positioner should start to blink. If not, verify wiring polarity and that the power supply is plugged in. Once the
NI card and Logix 3400IQ digital positioner are connected to the Fieldbus, the Logix 3400IQ digital
positioner should show up in the NI Configurator’s main window (as seen above). Wait for the small hour
glass icon that pops up next to each device and function block to go away. Under the Logix 3400IQ digital
positioner, four function blocks should be listed. Each function block should have the function block tag
name and type listed in apprentices. The four functions blocks are (AO)= Analog Out, (PID)= PID control,
(RB)= Resource block, and (FVPTB)= Flowserve Valve Positioner Transducer Block. If any of the blocks are
listed as unknown (UKN) the DDs are incorrect or not installed properly. If this occurred, try re-installing the
DDs, and restarting the NI-FBUS application.

NOTE: To view the transducer block, click the Transducer block icon.









7