4 to 20ma analog output retrofit, General information, 4 to 20 ma analog output retrofit – Flowserve Logix 1200e LGAIM0044 User Manual

Page 24: Figure 21: analog output board power

Advertising
background image

44-24

Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611

4 to 20 mA Analog Output Retrofit

General Information

The Logix 1200e digital positioner/controller can be
retrofitted to provide an analog feedback signal of the
stem position. This position feedback option has the
following features and specifications:

Does not interfere with positioner operation.

Zero and span adjustments of the feedback signal

are independent of the positioner and can be
adjusted manually.

Output follows actual position of valve, including all

failure modes of positioner except loss of power. An
output of 3.15 mA is transmitted with loss of power
to the analog output board.

Immune to RFI/EMI disturbances.

Can be retrofitted in the field.

CAUTION: Because the analog output board
shares common signals with the Logix internal
circuitry, the two units cannot be powered by
the same external power supply or by power
supplies that share a common reference.Gal-
vanic isolation of at least 50 VDC must be pro-

vided between the supplies powering the Logix
unit and the analog output board.

Available for explosion-proof and safe applications

(CSA, FM).

Masoneilan (Linear Actuators, cont.)

71 Domotor

25

10125644

50

10125645

100

10125646

88

6

10124595

16

10126752

47

B

10125702

48

B

10125702

“D” Domotor

200

10127467

71-2057AB-D

10129359

71-40413BD

10129461

Masoneilan (Rotary Actuators)

33

B

10125542

35

4

10125542

6

7

70

10

10125542

Vanguard

37/64

10127426

* Adjustable Mounting kit 10126736 may be needed if

handwheels are used.

Table VIII: Logix Mounting Kits (Continued)

Model

Size

Mounting Kit

Figure 21: Analog Output Board Power

Specifications

Potentiometer Range
of Rotation

40° to 95°

Power Supply Range

12.5 to 40 VDC
(24V DC typical)

Maximum Load
Resistance (ohms)

(Supply Voltage - 12.5) / 0.02

Current Signal Output

4-20 mA

Linearity

1.0% F.S.

Repeatability

0.25% F.S.

Hysteresis

1.0% FS

Operating
Temperature

-40° to 185° F
(-40° to 85° C)

Ambient
Temperature

For a 100° F (38° C) change in
ambient temperature, maximum
zero shift is 0.4% FS, maximum
span shift is 0.7% FS

Power Supply
Effects

Out put signal change is less than
0.05% FS when supply voltage is
varied between 12.5 and 40 VDC

Positioner Command
Current Loop
(Logix Input)

Position Feedback
Current Loop
(Logix Output)

+

+

R

Load

4 to 20 mA
Current Source

12.5 to
40 VDC
Power
Supply

+

+

CAUTION: Isolated power sources required.

Advertising