Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611

44-3

Unpacking

1. While unpacking the Logix 1200e positioner, check

the packing list against the materials received. Lists
describing the system and accessories are
included in each shipping container.

2. When lifting the system from the shipping con-

tainer, position lifting straps to avoid damage to
mounted accessories. Systems with valves up to
six inches may be lifted by actuator lifting ring. On
larger systems, lift unit using lifting straps or hooks
through the yoke legs and outer end of body.

WARNING: When lifting a valve/actuator assem-
bly with lifting straps, be aware the center of
gravity may be above the lifting point. There-
fore, support must be given to prevent the
valve/actuator from rotating. Failure to do so
can cause serious injury to personnel or dam-
age to nearby equipment.

3. In the event of shipping damage, contact the ship-

per immediately.

4. Should any problem arise, contact a Flowserve

Flow Control Division representative.

Logix 1200e Positioner Overview

The Logix 1200e digital positioner is a two-wire,
4-20 mA input, digital valve positioner. The Logix
1200e positioner also utilizes the HART protocol to
allow two-way remote communications with the posi-
tioner. The Logix 1200e positioner can control both
double and single-acting actuators with linear and
rotary mountings. Start up current must be at least
3.5 mA but once started, the Logix 1200e digital posi-
tioner operates with a signal as low as 2.8 mA. Below
2.8 mA, the operation and communication are sus-
pended.

Since the positioner is insensitive to supply pressure
changes and can handle supply pressures from 30 to
150 psig, a supply regulator is usually not required;
however, in applications where the supply pressure is
higher than the maximum actuator pressure rating a
supply regulator is required to lower the pressure to
the actuator’s maximum rating (not to be confused
with operating range). An air filter is required for all
applications due to the close clearances in the spool.

NOTE: The air supply must conform to ISA Standard
ISA 7.0.01 (a dew point at least 18 degrees Fahrenheit
below ambient temperature, particle size below five
microns – one micron recommended – and oil content
not to exceed one part per million).

Specifications

Table I: Electrical Specifications

Power supply

Two-wire, 4-20 mA 12.0 VDC

Compliance voltage

12.0 VDC

Effective resistance

625

@ 20 mA

Communications

HART Protocol

Minimum required
start-up current

3.5 mA

Minimum operating
current

2.8 mA

Maximum voltage

40.0 VDC

Table II: SoftTools Suite Software Specifications

Computer

Minimum Pentium processor running Win-
dows 95 or NT, 16-MB total memory
(32-MB recommended), 20-MB available
hard disk space, one CD-ROM drive

HART Modem RS-232 Modem or PCMCIA card

HART Filter

May be required in conjunction with some
DCSs

HART MUX

MTL 4840 system

Table III: Physical Specifications

Operating
Temperature Range

-40° F to +185° F
(-40° C to +85° C)

Housing

Cast, powder-painted aluminum,
stainless steel

Weight

8.3 pounds (3.9 kg) aluminum 20.5
pounds (9.3 kg) stainless steel

Table IV: Positioner Specifications

Dead band

<0.1% full scale

Repeatability

< 0.05% full scale

Linearity

< 0.5% (rotary), < 0.8%
(sliding stem) full scale

Air Consumption at

< 0.3 SCFM (0.5 Nm

3

/hr)@60 psig

(4 barg)

Table V: Hazardous Area Certifications

Explosion Proof

FM/CSA Class 1, Div 1, Groups B, C, D
CENELEC EExd IIB+H2 T5, IP-66

Non-incendive

FM/CSA Class 1, Div 2, Groups A, B, C,
D; CENELEC IIC Exn, T6,BS 6941,
IP-66, T

Intrinsically Safe

FM/CSA Class 1, Div 1, Groups A, B, C,
D; CENELEC EExib, T4 & T5, IP-66