NOTE: Custom characterization points can only be
entered by using ValTalk or SoftTools software. The
HART 275 handheld communicator will only allow the

user to enable or disable the currently stored custom
characterization.

Table III: Equal Percentage Curve Data

%

Command

% Control

Command

0

0.00

5

1.00

10

2.00

15

3.00

20

4.00

25

5.24

30

6.47

35

8.02

40

9.57

45

11.86

50

14.15

55

17.54

60

20.93

65

25.94

70

30.95

75

38.36

80

45.77

85

55.66

90

67.68

95

82.31

100

100.00

Table IV: Troubleshooting Logix 1200 Digital Positioner (1 of 3)

Failure or Problem

Probable Cause(s)

Refer to Section(s)

Mounting and Installation

LED does not blink

1. 4-20 mA input polarity may be

reversed

1. 4-20 mA input level may be too

low

1. Calibration is in process

1. See Electrical Wiring on

page 44-31. or Wiring and
Grounding guidelines on page
44-6.

1. See overview on page 44-4.

1. See Calibration on page 44-33..

Valve moves in wrong direction with no
input signal

1. Actuator is tubed for wrong air

action

1. Spool is stuck

1. See Air Action on page 44-32.

1. See Spool Valve on page 44-35.

Unit does not respond to analog 4-20
mA command

1. Unit is in digital command mode

1. Error occurred during calibration

1. See Theory of Operation on

page 44-30.

1. See Calibration on page 44-33.