Flowserve Logix 1200e LGAIM0044 User Manual

Page 43

Advertising
background image

Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611

44-43

Erratic communications

1. Maximum cable length or

impedance exceeded

1. HART modem not receiving

enough power. (laptop batteries
low)

1. Interference with I.S. barrier

1. See HART Communication on

page 44-35.

Alarms

Temperature

1. Ambient temperature has

exceeded electronics ratings

1. See Temperature Alarm on

page 44-37.

Hall sensor

1. Cable may have bad connection

1. Sensor may be damaged

1. See Hall Sensor Alarm on

page 44-37.

Modulator Current

1. Modulator minimum pressure

may be too low

1. Clogged orifice

1. Bad cable connection

1. See Modulator Current Alarm

on page 44-37.

EEPROM checksum

1. Error when reading non-volatile

memory storage

1. See EEPROM Checksum Alarm

on page 44-38.

Multiple Internal Flags

1. Bad micro-controller on main

PCB assembly

1. Replace main PCB assembly

LEDs

LED alternates between Green and
Red in normal operation

1. Modulator coil current may be

too high

1. Supply pressure may be close

to minimum of 30 psig (2.1 barg)

1. See Modulator Current Alarm

on page 44-37.

No LED blinks during calibration

1. Normal operation

1.

Yellow LED is blinking but valve posi-
tion is fine

1. User-defined limit may have

been reached; check alarm
screen

1. See Alerts on page 44-38.

Red LED is blinking on advanced
model, even though positioner has
pressure

1. Pressure below 30 psi (2.1 bar)

1. See Pressure Alarms on

page 44-38.

Advanced Features

Will not display pressure readings

1. Configuration not set to

Advanced

1. See Standard vs. Advanced

Diagnostics on page 44-40.

MPC will not function

1. Lower soft limit >= 0%.

1. 1% hysteresis around MPC set-

point being considered

1. See MPC (Minimum Position

Cutoff) on page 44-38.

Table IV: Troubleshooting Logix 1200 Digital Positioner (3 of 3)

Failure or Problem

Probable Cause(s)

Refer to Section(s)