Software

3.1 HART Protocol

The system uses the HART protocol to communicate over the HART network with other HART devices. The HART
protocol is a master/slave communication service for process control devices. HART digital signaling is an extension of
conventional analog signaling allowing the network signal to ride on the 4-20 mADC analog process signal. It uses
1200 bps binary phase-continuous Frequency-Shift-Keying (FSK), where a high frequency current is superimposed on
a low-frequency (typically 4-20 mADC) analog current.

3.2 HART Parameters

Table 3.1 – HART Parameters

Parameter

Value

HART Version

7.3

Expanded Device Type = Manufactuer ID + Device Type

0x3008

Physical Layer Supported

FSK

Physical Device Catagory

Actuator

Maximum Number of Burst Messages

3

Maximum Number of Event Messages

1

Size of the Event Queue

6

Maximum Number of Trends

2

Size of the Trend Buffer

12

Default Number of Preambles

1

5

3.2.1 Analog Input Ratings

Table 3.2 – Analog Input Ratings

Maximum current

2

30.0 mA

Maximum voltage

50 V

Current over-range
(Primary Variable Out of Limits)

Analog Input > 21 mA
Analog Input < 3 mA

(HART communication may fail, if Analog Input <2 mA.)

Multi-drop current draw

Approximately 2 mA

1. Field Device must have minimum 5 preambles, and maximum 20 preambles.
2. The analog input is automatically bypassed, if the maximum loop current is reached. The field device will continue to check the circuit for overload on a periodic basis,

and will restore the connection if the overload clears.