3 dynamic variables, 4 device variables, 2 field device status – Flowserve MX HART Field Unit User Manual

Page 20: 1 supported device variables

Advertising
background image

MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14

20

3.2.2 Field Device Status

The Field Device Status is contained in the second data byte in a Slave-to-Master frame as a bit field table. It indicates
the current operating status of the field device as a whole and is not associated with the completion of any command.

Table 3.3 – Field Device Status

Bit Mask

Description

0x01

Primary Variable Out of Limits – The PV is beyond its operating limit.

0x02

Non-Primary Variable Out of Limits – A device variable not mapped to PV is beyond its operating limits.

0x04

Loop Current Saturated – The loop current has reached its upper (or lower) endpoint limit and cannot increase (or

decrease) any further.

0x08

Loop Current Fixed – The loop current is being held at a fixed value and is not responding to process variations.

0x10

More Status Available – More status information is available via Command 48, Read Additional Status Information.

0x20

Cold Start – A power failure or Device Reset has occurred.

0x40

Configuration Changed – An operation was performed that changed the device’s configuration.

0x80

Device Malfunction – The device detected a serious error or a failure that compromises device operation.

3.3 Dynamic Variables

The Limitorque HART actuator device supports the following Dynamic Variables:

Table 3.4 – Supported Dynamic Variables

Variable Code

Variable

Direction

Physical Interface

0

PV (Primary Variable)

input

Analog current input – Analog Channel 0

1

SV (Secondary Variable)

output

None

2

TV (Tertiary Variable)

output

None

4

QV (Quaternary Variable)

output

None

3.4 Device Variables

3.4.1 Supported Device Variables

The Limitorque HART actuator device supports the following Device Variables:

Table 3.5 – Supported Device Variables

Variable

Code

Variable

Direction

Unit Code

Device Variable

Classification

Device Variable

Family

Range

0

Position setpoint

input

% (57)

Not Classified (0)

Valve/Actuator (6)

0-100

1

Current position

output

% (57)

Not Classified (0)

Not Used (250)

0-100

2

Torque

output

% (57)

Not Classified (0)

Not Used (250)

0-100

3

Motor temperature

output

°C (32), °F (33)

Temperature (64)

Not Used (250)

Not Limited

4

Compartment

temperature

output

°C (32), °F (33)

Temperature (64)

Not Used (250)

Not Limited