2 device variable mapping, 3 device variable units – Flowserve MX HART Field Unit User Manual

Page 21

Advertising
background image

21

MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14

flowserve.com

3.4.2 Device Variable Mapping

Device Variables may be mapped to the Dynamic Variables according to the following table:

Table 3.6 – Mapping of Device Variables to Dynamic Variables

Variable

Code

Dynamic

Variable

Direction Default Device Variable

Device Variables which may be mapped to the

Dynamic Variable

0

PV

input

Position Setpoint

Position Setpoint

1

SV

output

Current Position

Current Position or Torque

2

TV

output

Motor Temperature

Current Position, Torque, Motor Temperature or

Compartment temperature

3

QV

output

Compartment Temperature

Current Position, Torque, Motor Temperature or

Compartment temperature

No single Device Variable may be mapped to more than one Dynamic Variable.

For Example:

Valid Mapping:

Invalid Mapping:

PV = DV0

PV = DV0

SV = DV1

SV = DV1

TV = DV3

TV = DV1

QV = DV4

QV = DV4

If you try to map two Dynamic Variables to the same Device Variable, the command will return response code 2 “invalid
selection”. The Device Variables may be mapped from the DD menu Device Setup->Wired HART Board->Configuration->
Device Variable Mapping as follows:

Figure 3.1 – Device Variable Mapping Setup

3.4.3 Device Variable Units

Device Variables 0, 1, and 2 have fixed units that may not be changed. Device Variables 3 and 4 have units that may be
interchanged between °C and °F the default is °F. For Device Variables 3 and 4, the units may be changed from the DD menu
Process Variables->Wired HART Board as follows: