MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14

30

Command

Request Data Bytes

Response Data Bytes

No.

Description

Byte

Format

Description

Byte

Format

Description

46

Trim Loop

Current Gain

12

0-3

Float

Externally Measured Loop Current Level

(units of milliamperes)

0-3

Float

Actual Measured Loop Current Level (units of

milliamperes)

13

49

Write Primary

Variable

Transducer

Serial Number

14

0-2

Unsigned-24

Primary Variable Transducer Serial Number

0-2

Unsigned-24

Primary Variable Transducer Serial Number

50

Read Dynamic

Variable

Assignments

15

0

1

2

3

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Device Variable Assigned to the Primary Variable

Device Variable Assigned to the Secondary Variable

Device Variable Assigned to the Tertiary Variable

Device Variable Assigned to the Quaternary Variable

51

Write Dynamic

Variable

Assignments

0

1

2

3

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Device Variable Assigned to the Primary Variable

Device Variable Assigned to the Secondary Variable

Device Variable Assigned to the Tertiary Variable

Device Variable Assigned to the Quaternary

Variable

0

1

2

3

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Device Variable Assigned to the Primary Variable

Device Variable Assigned to the Secondary Variable

Device Variable Assigned to the Tertiary Variable

Device Variable Assigned to the Quaternary Variable

53

Write Device

Variable Units

16

0

1

Unsigned-8

Enum

Device Variable Code

Device Variable Units Code

0

1

Unsigned-8

Enum

Device Variable Code

Device Variable Units Cod

54

Read Device

Variable

Information

0

Unsigned-8

Device Variable Code

0

1-3

4

5-8

9-12

13-16

17-20

21

22

23-26

Unsigned-8

Unsigned-24

Enum

Float

Float

Float

Float

Enum

Enum

Time

Device Variable Code

Device Variable Transducer Serial Number

Device Variable Limits/Minimum Span Units

Code

Device Variable Upper Transducer Limit

Device Variable Lower Transducer Limit

Device Variable Damping Value

Device Variable Minimum Span

Device Variable Classification

Device Variable Family

Update Time Period

17

56

Write Device

Variable

Transducer

Serial No.

0

1-3

Unsigned-8

Unsigned-24

Device Variable Code

Device Variable Transducer Serial Number

0

1-3

Unsigned-8

Unsigned-24

Device Variable Code

Device Variable Transducer Serial Number

59

Write Number

of Response

Preambles

18

0

Unsigned-8

Number of preambles

0

Unsigned-8

Number of preambles

60

Read Analog

Channel and

Percent of

Range

0

Unsigned-8

Analog Channel Number Code

0

1

2-5

6-9

Unsigned-8

Enum

Float

Float

Analog Channel Number Code

19

Analog Channel Units Code = 39 (mA)

Analog Channel Level

Analog Channel Percent of Range

20

63

Read Analog

Channel

Information

0

Unsigned-8

Analog Channel Number Code

0

1

2

3

4-7

8-11

12-15

16

Unsigned-8

Enum

Enum

Enum

Float

Float

Float

Bits

Analog Channel Number Code

Analog Channel Alarm Selection Code = 250

(not used)

Analog Channel Transfer Function Code = 0

(linear)

Analog Channel Upper/Lower Range Values Units

Code = 57 (%)

Analog Channel Upper Range Value

Analog Channel Lower Range Value

Analog Channel Damping Value (seconds)

Analog Channel Flags

65

Write Analog

Channel Range

Values

21

0

1

2-5

6-9

Unsigned-8

Enum

Float

Float

Analog Channel Number Code

Analog Channel Upper/ Lower Range Values

Units Code

Analog Channel Upper Range Value

Analog Channel Lower Range Value

0

1

2-5

6-9

Unsigned-8

Enum

Float

Float

Analog Channel Number Code

Analog Channel Upper/ Lower Range Values

Units Code = 57 (%)

Analog Channel Upper Range Value

Analog Channel Lower Range Value

66

Enter/Exit Fixed

Analog Channel

Mode

0

1

2-5

Unsigned-8

Enum

Float

Analog Channel Number Code

Analog Channel Units Code

Fixed Analog Channel Level

22

0

1

2-5

Unsigned-8

Enum

Float

Analog Channel Number Code

Analog Channel Units Code = 39 (mA)

Fixed Analog Channel Level

23

67

Trim Analog

Channel Zero

0

1

2-5

Unsigned-8

Enum

Float

Analog Channel Number Code

Analog Channel Units Code

Externally Measured Analog Channel Level

0

1

2-5

Unsigned-8

Enum

Float

Analog Channel Number Code

Analog Channel Units Code = 39 (mA)

Fixed Analog Channel Level

23

68

Trim Analog

Channel Gain

0

1

2-5

Unsigned-8

Enum

Float

Analog Channel Number Code

Analog Channel Units Code

Externally Measured Analog Channel Level

0

1

2-5

Unsigned-8

Enum

Float

Analog Channel Number Code

Analog Channel Units Code = 39 (mA)

Fixed Analog Channel Level

23

71

Lock Device

0

Enum

Lock Code

0

Enum

Lock Code

76

Read Lock

Device State

0

Enum

Lock Status