Flowserve MX HART Field Unit User Manual

Page 26

Advertising
background image

MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14

26

Table 3.9 MX/QX Defined Status Bits

Device-Specific Status 0 – CMD 48 Bytes 0-3 : Hardware Faults

Bit

Description
Hardware Faults – these bits will trigger More Status Available bit

0

Main board to HART board communication loss

1

Reserved

2

Valve Jam

3

Over Torque in Close direction

4

Over Torque in Open direction

5

Phase Lost

6

Motor Temperature

7

Encoder Fault

8

Main board RAM error

9

Main board FLASH error

10

Main board EEPROM error

11

Reserved

12

Knob Failure

13

Limigard Fault

14

Contactor Fault

15

Power Board

16

Digital Out Board 1 (R1-R4 & RM) board fault

17

Digital Out Board 2 (R5-R8) board fault

18

Reserved

19

Analog Board 2 Fault

20

Reserved

21

Reserved

22

Motor Controller Fault

23

Reserved

24

Oil Over Temperature (arctic units)

25

Close Torque Timer Expired

26

Open Torque Timer Expired

27

HART Board 1 Fault

28

Reserved

29

HART Board 1 memory fault

30

Reserved

31

Future

Device-Specific Status 0 – CMD 48 Bytes 4-5 : Main Board Status

Main Board Status – these bits will not trigger More Status Available bit

0

Main board Self-test Ongoing (1=ongoing, 0=finished)

1

Main board Self-test Ok (1=succeeded, 0=failed; only valid if “Self-test ongoing = 0”

2

Future

3

Future

4

Future

5

Future

6

Future

7

Future

8

Future

9

Future

10

Future

11

Future

12

Future