Basic settings – Flowserve URB 1 User Manual

Page 29

Advertising
background image

29

Basic Settings

– continued –

0 % / 100 % calibration for capacitance level monitoring system

Press button three times briefly to enter
the window for calibrating the 0 % and
100 % settings.

Press button twice briefly to enter the
line editing mode.

Lower the water level in the vessel
to 0 %.

The split-screen main window shows
which GESTRA bus devices can be
displayed:

High level limiter NRS 1-41
Low level limiter NRS 1-40
Level switch NRS 2-40
Level controller NRR 2-40
Conductivity controller LRR 1-40

Before commissioning the installation
establish the measuring range of the
capacitance level electrode NRG 26-40 by
calibrating the 0 % and 100 % settings.

flashing

3 times briefly

twice briefly