Basic settings – Flowserve URB 1 User Manual

Page 59

Advertising
background image

59

Press button once briefly to activate the
line editing mode.

If the reading of the calibrated conductivity
meter does not tally the value indicated by
the URB 1 the compensation gradient has
to be changed until the two values agree.

Example: With a gradient of 1.9 % / °C the
two readings tally.

Press button once briefly to select the
digit “1”.

Press button once briefly to enter the line
where the linear temperature compensation
[% / °C] can be adjusted.

The factory set gradient 2.1 [% / °C] is
normally used for steam boilers operating
with constant pressure.

When the boiler is at full working pressure
compare the indicated value with the reading
of a calibrated conductivity meter – the two
values must tally.

Press button once briefly to move
the cursor one step further.

Basic Settings

– continued –

Adjusting LIN (linear) temperature compensation

– continued –

flashing

flashing

flashing

once briefly

once briefly

once briefly

once briefly