Basic settings – Flowserve URB 1 User Manual

Page 64

Advertising
background image

64

Press button once briefly to select the
function “start”.

Press button once briefly to finish the
configuration.

Raise temp./ pressure until the steam boiler
settles at full working pressure (in case of
variable pressure operation until the highest
operating pressure is reached).

The LRR 1-40 will now record the
temperature /conductivity values and saves
them as AUTO curve in the URB 1.

The number of recorded temp./conductivity
values is indicated in the line “Temp.”.

Press button once briefly to activate the
line editing mode.

Press button once briefly.

The recording of the AUTO curve is
finished once the steam boiler has
reached its working pressure.

In our example 15 temp./conductivity
values were recorded. A temperature of
181.7 °C was detected at the measuring
point of the conductivity electrode
LRG 16-40, which corresponds to a boiler
pressure of 10.3 bar.

Basic Settings

– continued –

Adjusting NORM (standard curve) temperature compensation

– continued –

flashing

flashing

flashing

once briefly

once briefly

once briefly

once briefly