Press button once briefly to select
the digit “1”.

Press button once briefly to accept the
configuration.

The standard curve “01” is now active.

The temperature values of the standard
curve “01” are based on the conditioning
agent caustic soda with a basic conductivity
of 260 µS/cm at 25 °C.

For more information see Annex (page 77).

Press button once briefly to move the
cursor one step further.

Press button once briefly to enter the line where
you can start recording the temperature/
conductivity curve that is characteristic of your
steam boiler.
The temp./conductivity values recorded by the
system cover the whole room temp. to service
temp. range.
In case of variable pressure operation we
recommend that you also record the AUTO curve.
If the standard curves are not suitable you can then
still use the AUTO curve.

Basic Settings

– continued –

Adjusting NORM (standard curve) temperature compensation

– continued –

flashing

flashing

once briefly

once briefly

once briefly

once briefly