Basic settings – Flowserve URB 1 User Manual

Page 40

Advertising
background image

40

Basic Settings

– continued –

Adjusting sensitivity of response

Press button twice briefly to activate
the line editing mode.

Use buttons and to toggle between
the two settings.

The split-screen window shows which
GESTRA bus devices can be indicated:

High-level limiter NRS 1-41

Low-level limiter NRS 1-40

Level switch NRS 1-42

Conductivity controller LRR 1-40

Before commissioning the installation
adjust the response sensitivity of the NRS
1-42.

The response sensitivities of the high-
level and low-level limiters are factory
set and cannot be changed.

Press button twice briefly to select
either of the following two response
sensitivities:

0.5

µ

S/cm

10

µ

S/cm

flashing

twice briefly

twice briefly