Operation – MMD Equipment 40S-8B1 User Manual

Page 25

Advertising
background image

4. Operation

4-4

A080516

Reset

4.2.4 Circuit protector (CP) for AVR protection

AVR is equipped with circuit-protector (CP) for

protection against overcurrent. Under the following
cases, it happens to function.



In case the machine gets overloaded while engine

speed is still lower.



In case the output voltage of generator is increased

higher than the specified voltage.

Symptom>



When circuit protector functions and load is applied

to the machine, such trouble as larger variance of
voltage and/or delayed voltage recovery follow.

How to reset>



Press the white colored AVR button inside the

control panel for resetting the circuit-breaker.

Note: Do not hold the button with such sharply pointed

things as a screwdriver, ball point pens etc.

Advertising
This manual is related to the following products: