background image

4. Operation

4-13

4.6 Unit Operation



Keep the door shut and locked when machine is in operation.



If opening the door is necessary, be careful not to touch rotating or hot parts. Burns or serious injury
could result.




After the engine starts up, warm up it under unload for approx. five minutes.



Warming up after starting up is necessary for smooth operation of the engine. Do not operate the
engine at full load immediately after it starts up. This will shorten the equipment life.



During the warm-up operation, examine the different parts of the equipment for any looseness, leakage
of water, oil, fuel, and other irregularities.



Also, make sure that the alarm lamps are off.



Be sure to operate the generator at a rated frequency, irrespective of the load capacity.
If the machine is operated with a frequency lower than the rated frequency, it could cause the generator
or to be burned.

4.6.1 Procedure to Start the Unit

Follow the starting procedure below.

<Manual operation>

Check and confirm that the circuit breaker“1”on the operation panel and the circuit breaker for

auxiliary receptacle at output terminal portion are both “OFF”.

Set the selector switch“2”to “MANUAL” operation position.

Turning the starter switch“3”to the “RUN” position, the engine starts preheating automatically.

When the preheating lamp“4”goes off, turn the starter switch“3”to “START” position and start

the engine.

Once engine has started, let it warm up about 5 minutes at no-load condition.

Adjust the voltage to the rated voltage by turning the voltage regulator knob“6”, watching the

voltmeter“5”.

Switch“ON”the circuit breaker“1”and also the circuit breaker for auxiliary receptacle and then

supply power to a load.

A100425

3 2 4 5 6 1