5. Periodic Inspection/Maintenance

5-6

5.5.2 Change engine oil filter

[At 50 hours for the first change and every 500 hours thereafter]

<Procedure>

When installing a new oil filter“1”, spread oil over

the packing“2”, and then screw it in. When the
packing touches the sealing surface, further
tighten the filter by approximately two-thirds turn
with a filter wrench.

After the oil filter“1”is assembled, check if there

are any oil leaks during operation.

(For part number, see 5.3)

5.5.3 Check GFCI receptacles

[Monthly or 250 hours operation, whichever comes first.]



If the generator is stored outdoors, unprotected from the weather, test the GFCI receptacle before
each use.



In case the GFCI has tripped due to the hazard of ground fault currents, investigate the cause and
correct it.

Regularly check the GFCI operation for safety.

<Procedure>

Unplug all appliances from the generator.

Start the engine.

Turn each single-phase and three-phase breaker ON.

Press the TEST BUTTON



The RESET BUTTON should extend with a click.



If the RESET BUTTON does not extend, contact your

nearest dealer.

Press the RESET BUTTON

When the RESET BUTTON extends during peration.



Unplug all appliances from the GFCI protected
receptacle.



Press the RESET BUTTON:

IF THE GFCI CANNOT BE RESET: The GFCI is faulty. Contact your nearest dealer.

IF THE GFCI RESETS PROPERLY: Check the appliance or the power cord.

Reset button

Test button

A040270

H000049

1

2