5. Periodic Inspection/Maintenance

5-14

5.6 Periodical Load Operation to be Performed

[Check and inspection upon each occurrence of the following phenomena]



Operating a generator for extended period with light load, less than 30 % or no load applied can

cause carbonization in the exhaust pipe, exhaust muffler and engine and also unburned fuel can

sometimes leak from the connection of exhaust pipe and from the outlet of the exhaust muffler. If

it continues at the same conditions, the leaked unburned fuel can cause a fire.



Further, accumulation and clogging of carbon in the exhaust muffler can degrade engine

performance and overheating to the engine, resulting in a serious accident. In case that such

phenomena occur, it should be continuously operated with load applied till the exhaust gas color

becomes generally gray and also till carbon accumulated in exhaust system can be eliminated,

being burnt.

(For load current, refer to the following table as an aim.)



Increase the load factor, step by step, paying attention to the exhaust conditions. Also watch the

surroundings because sometimes sparks of fire can come out from the exhaust pipe and the like.

Type SDG40S-8B1

SDG45S-8B2

Frequency Hz

60

Rated voltage

V

240

480

240

480

Load current

A

74

37

88

44