7 stopping procedures, Operation – MMD Equipment 400S-6B1 User Manual

Page 37

Advertising
background image

4. Operation

4-14

4.6.2 Meter and Indicator Lights while Operating

During normal operation, each indication of instruments is shown in the table below. Refer to the
table for daily checks.

Note; The values marked ※ vary with location of the voltage selector switch.

Monitor lamp

Indicator

lamp

Voltmeter

(V)

Frequency

meter

(Hz)

Ammeter

(A)

Oil

pressure

Water

temp.

Air filter

Turbo

protect

Diagnostic

Lamp

Glow

Before

Starting up

(preheatin

g)

0

0

0

Off

Off

Off

Off

Off

On

During

Operation

240

480

60

Less than

rated

current

Off

Off

Be sure to frequently check meters and indicators for
proper operation, or any machine water, oil, fuel leaks, etc.

The above table gives standard values. They may vary
slightly depending on operating conditions and other
factors.

In single-phase load operation, check the current of L1, L2,
and L3 phase with the ammeter, by turning the ammeter
change-over switch.
Each current should be balanced if unbalanced. Change
load connections so the current of L1, L2, and L3 is equally
balanced. Make sure that the current of each phase does
not exceed the rated one.

Lamp marked * glows while low speed idling is kept for a

few seconds by ambient temperature. (See 4-2)




4.7 Stopping Procedures

Procedure>

Switch “OFF” the breaker on the operation panel of the generator.

After performing cooling down operation about 5 minutes, place the starter switch to the “STOP”
position to stop the engine.

While the machine is kept unused, keep the operation selector switch placed to the “OFF” position.