Installation – MMD Equipment 150S-6A6 User Manual

Page 24

Advertising
background image

3. Installation

3-8

3.3.3 The Maximum Combined Simultaneous Power Consumption


Never exceed the maximum combined simultaneous power consumption.

The following chart shows the maximum power available from the 120V-20A GFCI receptacles
during simultaneous consumption (main terminals and receptacles) for both single or three
phase settings. Values shown in the left column give the maximum current available at the
120V-20A GFCI receptacles compared to the value of the simultaneous current consumption from
the main terminals.

SDG125S SDG150S

Single
Phase 120V-20A
GFCI Rcept.

Three Phase

240/480V

Single Phase

240/120V

Three Phase

240/480V

Single Phase

240/120V

kW kVA

kW

kVA

kW

0.0 125

72.0

150

87.0

1.2 121

70.8

146

85.8

2.4 117

69.6

142

84.6

3.6 113

68.4

138

83.4

4.8 108

67.2

133

82.2

Advertising
This manual is related to the following products: