2 troubleshooting, Maintenance/adjustment – MMD Equipment 150S-6A6 User Manual

Page 56

Advertising
background image

6. Maintenance/Adjustment

6-3

6.2 Troubleshooting

Should any trouble occur during operation, do not leave it. Investigate the cause and take

appropriate measures.

Read the manual carefully and fully understand what to do in case of trouble.

The better you understand the construction and function of the unit, the faster you can find a

problem and solution.

This chapter describes the state, cause and countermeasures of important troubles in detail

:

When “DIAGNOSTIC LAMP” turn on, push “DIAGNOSTIC BUTTON” and check “FAULT CODE”.

See “OPERATOR

S MAUAL” and research the cause of trouble.

Symptom Cause Counter

measures

Starter does not
rotate. Low starter
revolution speed
even when
starting.

(1)Battery malfunction

Check Battery →

Charge/Change

Starter rotates but
engine does not
start up.

(1)Fuel filter clogging
(2)Fuel pre-filter clogging
(3)No diesel fuel oil
(4)Air mixing in fuel pipings

Disassemble, clean, and change
Disassemble, clean, and change
Replenish fuel
Bleed air

Engine oil
pressure drop
warning lamp
glows.

(1)Engine oil shortage
(2)Engine oil filter clogging
(3)Oil pressure switch malfunction
(4)Loosened or disconnected wiring, or

connector

Replenish fuel
Change
Change
Check/repair

Coolant
temperature rise
warning lamp
glows.

(1)Radiator clogging
(2)Faulty thermostat
(3)Faulty coolant temperature switch
(4)Shortage of coolant
(5)Slip of fan belt
(6)Looseness, disconnection of wiring or

connectors

Clean
Change
Change
Replenish
Adjust tension
Check/repair

Leakage warning
lamp glows.

(1) Leakage on generator side
(2) Leakage on load side
(3) Leakage on connecting cable
(4) Defective leakage relay

Check/repair
Check/repair
Check/repair
Check/repair

The warning lamp
for air filter
clogging flickers.

(1) Air filter clogging

Clean